AQ-101LV Arc flash Protection Device

AQ-101LV arc flash protection device is a sophisticated microprocessor-based arc flash protection unit for arc light detection. It is designed to minimize the damage caused by an arcing fault (arc flash) by tripping the circuit breaker that sources the fault current. The complete system self-supervision function of AQ-101LV provides the highest level of dependability by continuously monitoring all internal system functions as well as with external connections.

Read More
Description:

The AQ-101LV arc flash protection device acts as a sub-unit to AQ-110P in an AQ 100 arc protection system. It can also function as a stand-alone unit in light-only systems.

Features:
  • A wide range for the power supply (18…72 V DC or 92…265 V AC/DC).
  • A maximum of 12 arc light point sensors (3 point sensors per channel).
  • A maximum of 1 fiber loop sensor (optional).
  • 4 trip relays.
  • 1 system failure relay.
  • 1 fast binary output.
  • 2 fast binary inputs.
  • 1 multifunction push button.
  • Non-volatile memory.
  • 12 indication LEDs.

Technical Data

  • Light (L>)
  • Light and pressure (L> / P>)
  • Circuit breaker failure protection (50BF/52BF)
  • Total trip time when using mechanical trip relays: 7 ms (only arc light signal from an AQ-110x device)
  • Total trip time when using mechanical trip relays: 7 ms (both overcurrent and arc light signal from an AQ-110x device)
  • Reset time (arc light stage): 2 ms
  • Protection operational after power up: 88 ms

  • Applicable sensors
  • AQ-01 light sensor (activation thresholds: 8 klx, 15 klx, 50 klx)
  • AQ-02 light and pressure sensor (activation thresholds: 8 klx, 15 klx, 50 klx)
  • AQ-06 plastic fiber sensor (3...40 m) (optional)
  • AQ-07 glass fiber sensor (3-50 m length) (optional)
  • AQ-08 glass fiber sensor (3...15 m) (optional)
  • Trip relays (T1, T2, T3, T4)
  • 3 NO + 1 NC or 4 NO
  • Rated voltage: 250 V AC/DC
  • Continuous carry: 5 A
  • Make-and-carry for 3 s: 16 A
  • Make-and-carry for 0.5 s: 30 A
  • Breaking capacity DC (when L/R = 40 ms): 40 W; 0.36 A at 110 V DC
  • Contact material: AgNi 90/10
  • Binary output (BO1)
  • Number of outputs: 1
  • Rated voltage: +24 V DC
  • Maximum rated current: 20 mA
  • Binary inputs (BI1, BI2)
  • Number of inputs: 2
  • Threshold voltage: 24 V DC
  • Rated voltage: 250 V AC/DC
  • Rated current: 3 mA
  • Power supply
  • Auxiliary power supply: 92…265 V AC/DC
  • Auxiliary power supply: 18…72 V DC (optional)
  • Maximum interruption: 100 ms
  • Maximum power consumption: 5 W
  • Standby current: 90 mA

  • 12 indication LEDs
  • Multifunction push button (SET)
  • Autoconfiguration
  • Indication reset
  • System check

  • Sensors and wiring
  • Binary I/O
  • Trip coil
  • Power supply
  • Internal voltages
  • Settings

  • AQ 200 series
  • AQ 300 series
  • AQ 100 series

  • AX016 Wall mounting bracket
  • Are you a serious well-wisher of your production unit? know the emotions from our existing customers.
  • Would you wish critical spares be always in-hands ensuring continuous plant operations without any interruption?
  • Would you like to receive your machineries / routine spares at most economical pricing?
  • How expensive is peace of mind having Arc fault free electrical systems in your premises?

Reach us to know

Request a call back