Arcteq has developed different types of arc sensors that are usable with different AQ 100 series devices. They are all compatible with different types of switchgear according to the specific application requirements. The available sensor types are arc light fiber optic loop sensors (AQ-06, AQ-07 and AQ-08).
Read MoreDescription :
There are three types of fiber loop sensors :
- AQ-06, a plastic fiber loop sensor.
- AQ-07, a glass fiber loop sensor.
- AQ-08, a glass fiber loop sensor for high temperature applications.
Technical Data
- Material: plastic fiber
- Light intensity threshold: 8,000 lx
- Detection radius: 360 degrees
- Cable length: 3...40 m
- Cable diameter: 1.0 mm
- Bending radius: 5 cm
- Operating temperature: –40...+85 °C
- Material: covered glass fiber
- Light intensity threshold: 8,000 lx
- Detection radius: 360 degrees
- Cable length: 3...50 m
- Cable diameter: 1.2 mm
- Bending radius: 1 cm
- Operating temperature: –40...+85 °C
- Material: covered glass fiber
- Light intensity threshold: 8,000 lx
- Detection radius: 360 degrees
- Cable length: 3...15 m
- Cable diameter: 1.2 mm
- Bending radius: 1 cm
- Operating temperature: –40...+125 °C